"STOPPED! Overcurrent" Message on LCD Screen

If the LCD screen displays the message: “STOPPED! Overcurrent” for your PULSE 500 Series door operator, it indicates that the operator thinks the door is using more current than usual, typically an indication of hitting an obstacle or an unbalanced door. To solve the issue, try the following:
  • First, check that the door’s path and rails are clear of any obstacles.
  • If they are already clear, run a BALANCE CHECK from the ADVANCED MENU to check the door’s balance.
  • If the door is balanced, the ratio between the 2 numbers displayed on the LCD screen under Open and Close should be under 10%.
  • If the door is still overcurrenting, recalibrate the door under the ADVANCED MENU.
  • You can also try to increase the Closing/Opening Force under the ADVANCED MENU.

Related Articles

Leave feedback on this article








Need more assistance?

  Click to Chat Now

Still can’t find the information you need?


By clicking “Allow All Cookies”, you agree to the storing of cookies on your device to enhance site navigation, analyze site usage, and assist in our marketing efforts. For more information please refer to our Privacy Notice.

iControls Inc. Logo

Privacy Preference Center

When you visit iControls.ca, we may store or retrieve information on your browser, mostly in the form of cookies. This information might be about you, your preferences or your device and is mostly used to make the site work as you expect it to. The information does not usually directly identify you, but it can give you a more personalized web experience. Because we respect your right to privacy, you can choose not to allow some types of cookies. Click on the different consent preferences below to find out more. As a reminder, blocking some types of cookies may impact your browsing experience on iControls.ca.

For more information, please refer to our Privacy Notice .

Manage Consent Preferences