Door Stops at the Wrong Position During Opening

If the door stops at the wrong position during opening with an LCD message of "Stopped: Overcurrent" for your PULSE 200 Series door operator, consider the following troubleshooting actions:

For overly sensitive Opening Force:

  • Navigate to the STARTUP MENU and adjust the Opening Force setting to suit your needs.
  • For the commercial model: choose a value between 1 (most sensitive) and 99 (least sensitive).
  • For the residential model: choose a value between 1 (most sensitive) and 50 (least sensitive).

For obstructions causing door jam:

  • Inspect the door's path for any external objects or obstructions that might be activating the Opening Force setting. If you find any, remove them to ensure smooth operation.

Related Articles

Leave feedback on this article








Need more assistance?

  Click to Chat Now

Still can’t find the information you need?


By clicking “Allow All Cookies”, you agree to the storing of cookies on your device to enhance site navigation, analyze site usage, and assist in our marketing efforts. For more information please refer to our Privacy Notice.

iControls Inc. Logo

Privacy Preference Center

When you visit iControls.ca, we may store or retrieve information on your browser, mostly in the form of cookies. This information might be about you, your preferences or your device and is mostly used to make the site work as you expect it to. The information does not usually directly identify you, but it can give you a more personalized web experience. Because we respect your right to privacy, you can choose not to allow some types of cookies. Click on the different consent preferences below to find out more. As a reminder, blocking some types of cookies may impact your browsing experience on iControls.ca.

For more information, please refer to our Privacy Notice .

Manage Consent Preferences